Basic Functions
The KF86P is a multipurpose, light-weight, field portable test set, it capable of testing a wide variety of electro-mechanical, solid state and microprocessor based protective relays, motor overload relays, IEC61850 testing, and similar protective devices.
Advance Feature
Key Points
Innovative“Plug and Play ”After-sales Service Advantages:
The KF86P protection relay tester, which utilize innovative technology, module design, and a simple internal structure, ensuring a higher level of product quality and providing assurance for a three-year warranty commitment. Besides, it also contributes to achieving the quality objective of a 15-year product service life.For after-sales maintenance, only module replacement is required, and there is no need for accuracy calibration after module replacement. Once assembly is complete, it can be used directly, truly achieving "Plug and Play".
Public disclosure, the internal structure is visualized as shown in the following diagram:
AC current source | |
Amplitude & Power | 6×35A @ 424VA max each; 3×70A @ 670VA max each; |
Accuracy | <0.015%Rd+0.005%Rg Typ. <0.04%Rd+0.01%Rg Guar. |
Range | Range I: 3A Range II: 35A Automatic Range |
DC Offset | <3mA Typ./ <10mA Guar |
Resolution | 1mA |
Distortion | <0.025%Typ. / <0.07% Guar. |
Ascends/Descent response | <100us |
DC Current source | |
Amplitude & Power | 3×20A @ 400W max |
Accuracy | ±5mA @ <1A ±0.2% @ ≥1A |
Ascends/Descent response | <100us |
AC voltage source | |
Amplitude & Power | 6×310V @ 105VA max each |
Accuracy | <0.015%Rd+0.005Rg Typ. <0.04%Rd+0.01Rg Guar. |
Range | Range I: 30V Range II: 310V Automatic Range |
DC Offset | <10mV Typ./ <60mV Guar |
Resolution | 1mV |
Distortion | <0.015%Typ. / <0.05% Guar. |
Ascends/Descent response | <100us |
DC Voltage source | |
Amplitude & Power | 6×350V @ 100W max 3×700V @ 150W max |
Accuracy | ±10mV @ <5V ±0.2% @ ≥5V |
Ascends/Descent response | <100us |
Frequency & Phase Angle | |
Frequency Range | DC ~ 1000Hz, 3000Hz transient |
Frequency Accuracy | ±0.5ppm |
Frequency Resolution | 0.001Hz |
Phase Range | -360°~360° |
Phase Accuracy | <0.02° Typ. / <0.1° Guar. 50/60Hz |
Phase Resolution | 0.001° |
Auxiliary DC Supply (Battery Simulator) | |
Range | 8 ~ 60Vdc (Max Load Current 1.16A) Accuracy<2% 60 ~ 120Vdc (Max Load Current 0.58A) Accuracy<1% 120 ~ 350Vdc (Max Load Current 0.2A) Accuracy<0.5% |
Power | >69W max |
Resolution | 10mV |
Protection | Short-circuit protection |
Overload Protection | Yes |
Isolation | Isolated from other terminal |
Binary input | |
Electrical isolation | 10 pairs of electrical isolated each |
Input impedance | 5 kΩ…13kΩ(Empty contact) |
Input feature | 0 V~300Vdc Or dry contact (Binary 1~4 inputs turn over potential can be programmable) |
Sampling Rate | 10kHz |
Time resolution | 10us |
Time measurement range | infinity |
Time accuracy | ±1ms @ <1s ±0.1% @ ≥1s |
Debounce time | 0~25ms (Software controlled) |
Binary Output | |
Quantity | 4 pairs |
Type | Fast speed transistor, programmable software control |
AC break capacity | Vmax:250V(AC)/ Imax:0.5A |
DC break capacity | Vmax:250V(DC)/ Imax:0.5A |
Electrical isolation | All pairs isolated |
Time Synchronization | |
Satellite synchronization | 1 × SMA,Use for GPS antenna interface Support GPS and Beidou Satellite |
Fiber IRIG-B | 2 × ST,1 for transmission, 1 for receiving |
Electric IRIG-B | 1 × 6Pin 5.08mm phoenix terminal 1 for transmission, 1 for receiving |
External trigger synchronization | 1 × 4Pin 5.08mm phoenix terminal external trigger input + external trigger output |
Sync error | <10us |
Communication interface | |
Ethernet | 2 × RJ45 ,10/100M |
WIFI | Inbuilt WIFI DHCP service |
Serial port | 1 × RS232 |
USB | 2 × USB2 |
Weight & Size | |
Size | 390mm×256mm×140mm |
Weight | 10kg |
Display | 9.7inch LCD, touch screen |
Keypad | Number key + direction key |
Power supply | |
Nominal voltage | 220V/110V (AC) |
Allowable voltage | 85 - 265 VAC ;127V~350V(DC) |
Nominal Frequency | 50Hz |
Allowable Frequency | 47-63Hz |
Current | 10A max |
Power Consumption | 1200VA max |
Connection Type | Standard AC socket 60320 |
Working environment | |
Operating temperature | -10~+55 ℃ |
Relative humidity | 5~95%,Non-condensation |
Storage temperature | -20℃ ~ +70℃ |
Atmospheric pressure | 80kPa~110 kPa(altitude 2000m or lower) |
● | Fully complying IEC61850 Sampling value and GOOSE; (IEC61850-9-1, IEC61850-9-2/(LE), IEC60044-7/8) |
● | Able to simultaneously output sampling value and analog signals, or subscriber and publish GOOSE message and relay contact binary I/O function. |
● | Up to 36 sampling value channels can be mapped. |
Fiber port (LC type) | |
Type | 100Base-FX (100Mbit,Fiber, full duplex) |
Port Number | 8 Pairs |
Cable model | 62.5/125μm(Multiple-mode fiber, orange) |
Wave length | 1310nm |
Transmission distance | > 1Km |
Status indication | SPD Green (lights): active connection Link\AcT Yellow (blinking): data exchange |
Low-level signal output | |
Output channels | 10 channels, 8 Voltage outputs + 2 Current outputs |
Output port type | Phoenix terminal |
Output range | 8x0~8Vrms; 2x0~20mA |
Accuracy | (0.01~0.8 Vrms/0~2mA):<0.05% Typ. / <0.1% Guar. (0.8~8 Vrms/2~20mA): <0.02% Typ. / <0.05% Guar. |
Resolution | 250µV |
Harmonic(THD%) | < 0.05% Typ. / <0.1% Guar. |
Frequency range | DC~1.0kHz, transient 3KHz |
Frequency accuracy | 0.002%(Normal frequency) |
Frequency resolution | 0.001Hz |
Phase range | 0~359.9° |
Phase accuracy | <0.02°,50/60Hz |
Phase resolution | ±0.001° |
DC Measurement Input | ||
Voltage Input | Range | 0~±10V dc |
Max Input | ±11V dc | |
Accuracy | Accuracy <0.05% rg Typ. <0.02% rg Guar. | |
Input Impedance | 1M ohm | |
Current Input | Range | 0~±1mA / 1~±20mA, auto range |
Max Input | 600mA | |
Accuracy | Accuracy <0.05% rg Typ. <0.02% rg Guar. | |
Input Impedance | 15 ohm |
Energy Meter Calibration | |
Sensor Usage | Mechanical meters / Electronic meters |
Sensor Output | High lever:>4.5V, Low level:<0.2V |
Pulse Input | 1 pulse input port, 5Vdc high level valid only. |
Pulse Range | 500KHz pulse input Max. |
Pulse Output | 1 Transistor output, Open-collector, 5Vdc/5mA |