Host Device’s functions and characteristics |
Transient true RMS value |
Current Each single phase and combined phase, average value |
Phase voltage/Line voltage Each single phase and combined phase, average value |
Frequency 45~65Hz |
Max/Min VALUE |
Max/Min CURRENT RMS |
Max/MinVOLTAGE RMS |
Max/Min Frequency |
Max/Min THD I and THD U |
Demand and peak value |
Current per phase the present value/peak value/monthly peak value |
Power quality |
(THD) current and voltage |
1-31times harmonic analysis current and voltage |
Voltage crest factor CF and current K factor |
Event record |
100pcs SOE event record |
Alarm system |
8 warning channels with configurable limit value |
4 warning channels with configurable logic |
Communication |
RS-485 /MODBUS-RTU Protocol |
Display |
Large screen STN liquid display |
Real time clock |
Year, month, date, minute, second |
Others |
Support program online upgrade |
Auxiliary module features |
DI input module (optional) |
2-channel DI input (Dry Contact) |
Relay (DO) output module (optional) |
1-channel relay output, which can be set by local over-limit alarm or by remote control |
Analog input (AI)/output (AO) module (optional) |
1 Channel only Being optional for 4-20mA DC analog input, 0-5V DC analog input, 4-20mA DC analog output |
Electrical characteristics | ||
Measure Type | 3P3W ACsystem,3P4W ACsystem | |
Sampling rate | 128 points per cycle | |
Data refresh rate | 1S | |
Measure accuracy | Current | ±0.2%FS |
Voltage | ±0.2%FS | |
Power | 0.5S | |
Frequency | ±0.001Hz | |
DC input (AI) |
0.5% FS | |
DC output (AO) |
0.5% FS | |
Input voltage characteristics | Measure Voltage |
3 *220/380V(Directly input) |
3 * 57.7/100V(PT secondary side) | ||
Allowed overload capability | 1.2 times/continuous | |
Input resistance | 300KΩ/phase | |
Input current characteristics |
Measure current |
5A (CT Secondary side)Or 1A (CT Secondary side) |
Allowed Overload capability |
1.2 times/continuous | |
Input resistance | <0.1Ω | |
Binary input | Working valtage | 15 VDC |
Input resistance |
12KΩ | |
Isolation valtage |
2KV | |
Relay Output | Node type | Mechanical contact |
Node capability | 220 VAC/5A、30 VDC/5A | |
4-20mA DC input measurement |
Measure current | 4-20mA |
Allowed Overload capability |
1.2 times/continuous | |
Input resistance | 10Ω | |
Isolation voltage |
2KV | |
0-5V DC input measurement |
Measure voltage |
0-5V |
Allowed Overload capability |
1.2 times/continuous | |
Input resistance | 12.5KΩ | |
Isolation voltage |
2KV | |
4-20mA DC output |
Open-circuit | 15VDC |
Load capability | ≤600Ω | |
Isolation voltage |
2KV | |
Power supply | AC | 85~264 VAC/45-65Hz |
DC | 100~375 VDC | |
Power consumption | < 3W | |
Mechanical performance | ||
weight | <0.5kg | |
IP protection Level | Meter Panel IP52 Meter Host IP30 |
|
Dimension | Host | 75 X 75 X 113 mm |
Working temperature |
Display screen | -20~70℃ |
Meter | -25~70℃ | |
Storage temperature |
Meter+display screen | -40~85℃ |
Relative humidity | 5% - 90%RH,No condensation | |
EMC | ||
Antistatic discharge interference |
IEC 61000-4-2,Level 4 | |
Anti-fast transient group pulse |
IEC 61000-4-4,Level 4 | |
Anti-surg | IEC 61000-4-5,Level 3 | |
Resistance to power frequency magnetic field | IEC 61000-4-8,Level 3 | |
Electrical insulation performance | ||
Insulation resistence | GB/T13729,>50MΩ | |
Power frequency withstand | GB/T13729,AC 3KV 50Hz /1min | |
Impulse voltage | GB/T13729,5KV,1.2/50us |
Model specification:PMC72S-①-②-③-④-⑤ | |
① Model code: | |
1 | 57.7/100V Rated measurement voltage,5A Rated measurement current。 |
2 | 57.7/100V Rated measurement voltage,1A Rated measurement current。 |
3 | 220/380V Rated measurement voltage,5A Rated measurement current。 |
4 | 220/380V Rated measurement voltage,1A Rated measurement current。 |
② Model code: | |
1 | Power supply:85~264 VAC/45-65Hz,100~300 VDC |
③ Model code: | |
0 | Without DI |
2 | 2 Channels DI |
④ Model code: | |
0 | Without relay output |
1 | Optional 1 Channel relay output |
⑤ Model code: | |
ab | ab is a 2 integer,a means AI01 port optional for AI/AO modules,b means AI02 port optional for AI/AO 0–none 1 -0-5VDCanaloginputmeasure(AI) 2 -4-20mA DC analog input measure(AI) 3 -4-20mA DC analog output(AO)For example:ab=00,Means AI01 port is not equipped with AI/AO module,AI02 port is not equipped with AI/AOmodule ab =01,Means options 0-5V DC analog input measure; |