English

PMC96 series three-phase electric monitoring meter

Item No.: 206010
PMC96 series three-phase electric monitoring meter adopts Segment type LCD screen、beautiful and grand,high contrast; With high-speed processor as the core, measurement of electric parameters using 22 AD, electric energy metering, wide dynamic range, high accuracy. Can optional configure various binary、relay、RS-485 communication module, can easily fulfill the integration of various intelligent distribution system.
Description specification ordering instruction
Features
Adopts 22 AD for achieve electric parameter measurement, electric energy metering, wide dynamic range, high accuracy;
Electric parameter over-limit alarm monitoring, alarm output relay association;
Support 2-channel DI/DO,1 channel electric energy pulse output;
Support MODBUS-RTS standard protocol, RS485 communication.
 
Series Model
PMC96S-I Three-phase digital current meter
PMC96S-U Three-phase digital voltage meter
PMC96S-P Three-phase digital power meter
PMC96S-C Three-phase digital power factor meter
PMC96S-Z Three-phase electric monitoring meter
PMC96SL-I Three-phase LCD screen current meter
PMC96SL-U Three-phase LCD screen voltage meter
PMC96SL-P Three-phase LCD screen power meter
PMC96SL-C Three-phase LCD screen power factor meter
PMC96SL-Z Three-phase electric monitoring meter
 
Applications
Industrial distribution automation system
Power plant auxiliary system
Substation automation system
Energy management system
Intelligent mansion electrical engineering
Switch gear of high & low voltage
 
Product Model PMC96L-Z
PMC96-Z
PMC96L-C
PMC96-C
PMC96L-P
PMC96-P
PMC96L-U
PMC96-U
PMC96L-I
PMC96-I
Instantaneous real virtual value          
Current   Single phase & neutral line    
Voltage   Line/line & Phase/line    
Frequency        
Active power  3-phase & Single phase      
Reactive power 3-phase & Single phase        
Power factor  3-phase & Single phase      
Energy          
Active energy  1 channel pulse output        
Reactive energy        
Communication          
MODBUS-RTU protocol
Display          
LCD or Digital display
Other          
Support program online upgrade
Optional function          
1 channel RS485
2-channel DI
2-channel DO
2-channel limits alarm  
 
 
Electrical Characteristics
Measurement type Three-phase three-wire AC system
Three-phase four-wire AC system
  Sampling rate: 64 times per cycle
Data refresh rate 1S
Measurement Accuracy Current 0.5%
Voltage 0.5%
Power 0.5%
Frequency 0.05Hz
Active Energy 1.0%
Reactive Energy 2.0%
AO 1%
Input voltage characteristics
 
Measuring voltage 3 X 220/380V(connected directly)
3 X 57.7/100V(connected by CT)
Allowed load 1.2 times / continuous
Input impedance 1.8MΩ
Input current characteristic Measuring current 5A or 1A (connected by CT)
Allowed load 1.2 times / continuous
Input impedance <0.1Ω
Binary input Working voltage Passive dry contactbuilt-in+15VDC power supply
Input impedance 5KΩ
Isolation voltage 2KV
Relay output Node type Mechanical shock
Node capacity 220 VAC/5A  30 VDC/5A
Working power supply AC 85~265 VAC/45-65Hz
DC 100~300 VDC
Power dissipation < 3W
Mechanical Properties
Weight 0.5kg
IP protection grade Panel IP52, body IP30
Size 96X 96 X 102mm
Operating temperature -10~55
Storage temperature -20~70
Relative humidity 5% - 90%RH,No condensation
EMC
Electrostatic discharge interference IEC 61000-4-2,Level 4
Group of anti-fast transient pulse IEC 61000-4-4,Level 4
Anti-impact IEC 61000-4-5,Level 3
Anti-frequency magnetic field IEC 61000-4-8,Level 3
Electrical insulation performance
Insulation resistance GB/T13729,>50MΩ
Frequency withstand voltage GB/T13729AC 2KV 50Hz /1min
Impulse voltage GB/T137295KV1.2/50us
 
SPECIFICATION:  PMC96A-B-C-D-E-F
A Model specification:
PMC96L LCD Display
PMC96 Digital Display
B Means type
I 3-Phase current meter
U 3-Phase voltage meter
P 3-Phase power meter
C 3-Phase power factor meter
Z 3-Phase power monitoring meter
C Means Rated measurement voltage, current
1 57.7/100V, 5A
2 57.7/100V, 1A
3 220/380V, 5A
4 220/380V, 1A
D System frequency
1 50Hz
2 60Hz
E Working power supply
1 100~300VDC, 85~265VAC/45~65Hz
F Optional function
S 2-Channel Binary Input
R 2-Channel Relay Output
C 1 Channel RS485
Example: order model is: PMC96L-I-3-1-1-SR
It means PMC96L 3-phase LED display current meter has rated measuring is 220/380V 5A, system frequency 50Hz,power supply is 85~265VAC/45~65Hz,option is 2-channel binary input and 2-channel relay output.