Host function and characteristic |
Transient true RMS value |
Current Each single phase and combined phase, average value |
Phase voltage/Line voltage Each single phase and combined phase, average value |
Active, reactive, apparent power Sum of each single-phase and three-phase |
Power factor Sum of each single-phase and three-phase |
Frequency 45~65Hz |
MIN/MAX VALUE |
MIN/MAX CURRENT RMS |
Maximum/minimum phase voltage RMS |
Maximum/minimum total active, reactive, apparent power |
Max/Min total power factor |
Max/Min Frequency |
Max/Min THD I和THD U |
Demand and peak value |
Current per phase the present value/peak value/monthly peak value |
Total active power, total reactive power, total apparent power the present value/peak value/monthly peak value |
Energy |
Input/ output/ active electric energy 1 channel pulse output Input output active electric energy 1 channel pulse output |
Input/ output/ reactive electric energy 1 channel pulse output active electric energy 1 channel pulse output |
apparent power |
monthly energy |
Electric energy multi-rate |
8 multi-rate time, 4 rates can be set |
Power quality |
THD current and voltage |
1-31 times harmonic analysis |
Voltage crest factor CF and current K factor |
Event record |
100pcs SOE event record |
Warning alarm system |
8 warning channels with configurable limit value |
4 warning channels with configurable logic |
Communication |
RS-485 /MODBUS-RTU Protocol |
Display |
Large screen STN liquid display |
Real time clock |
Year, month, date, minute, second |
Others |
Support program online upgrade |
Auxiliary module features |
Analog I/O (DI) input module (optional) |
2-channel Analog I/O input |
Relay (DO) output module (optional) |
2-channel relay output, which can be set by local over-limit alarm or by remote control |
Analog input (AI)/output (AO) module (optional) |
2 Channels in total Being optional for 4-20mA DC analog input, 0-5V DC analog input, 4-20mA DC analog output The first analog port (A1 port) is located at the same (DI) port of Binary Input, so user only can select either one of the two but can’t select both |
Electrical characteristics | ||
Measure type | 3P3W AC system, 3P4W AC system; |
|
Samping rate | 128 points per cycle | |
Data refresh rate | 1S | |
Measure accuracy |
Cureen | ±0.2%FS |
Voltage | ±0.2%FS | |
Power | 0.5S | |
Frequency | ±0.001Hz | |
Active Energy | 0.5S | |
Reactive Energy | 1.0S | |
DC input(AI) | 0.5% FS | |
DC output(AO) | 0.5% FS | |
Input voltage characteristics |
Measure Voltage | 3 *220/380V(Directly input) |
3 * 57.7/100V(PT secondary side) | ||
Allowed overload capability |
1.2times / continuous | |
input resistance | 300KΩ/phase | |
Input current characteristics | Measure current |
5A (CT Secondary side)Or 1A (CT Secondaryside) |
Allowed overload capability | 1.2 times/continuous | |
input resistance | <0.1Ω | |
Binary input | Working voltage |
15 VDC |
input resistance | 12KΩ | |
Isolation voltage | 2KV | |
Relay Output | Node type | Mechanical contact |
Node capability | 220 VAC/5A、30 VDC/5A | |
4-20mA DC input measurement |
Measure current | 4-20mA |
Allowed overload capability |
1.2 times / continuous | |
input resistance | 10Ω | |
Isolation voltage |
2KV | |
0-5V DC input measurement | Measure Voltage | 0-5V |
Allowed overload capability |
1.2times / continuous | |
input resistance | 12.5KΩ | |
Isolation voltage | 2KV | |
4-20mA DC output |
Open-circuit Voltage | 15VDC |
Load capability | ≤600Ω | |
Isolation voltage | 2KV | |
Power supply | AC | 85~264 VAC/45-65Hz |
DC | 100~375 VDC | |
Power consumption | < 3W | |
Mechanical performance | ||
Weight | 0.5kg | |
IP Protection Level | Meter Panel IP52,Meter Host IP30 | |
Dimension | Host | 96 X 96 X 72 mm |
Host+modules | 96 X 96 X 120 mm | |
Working temperature | Display screen | -20~70℃ |
Meter | -25~70℃ | |
Storage temperature | Meter+display screen | -40~85℃ |
Relative humidity | 5% - 90%RH, No condensation | |
EMC | ||
Antistatic discharge interference | IEC 61000-4-2,Level 4 | |
Anti-fast transient group pulse | IEC 61000-4-4,Level 4 | |
Anti-surge | IEC 61000-4-5,Level 3 | |
Resistance to power frequency magnetic field | IEC 61000-4-8,Level 3 | |
Electrical insulation performance | ||
Insulation resistance | GB/T13729,>50MΩ | |
Power frequency withstand Voltage | GB/T13729,AC 3KV 50Hz /1min | |
Impulse voltage | GB/T13729,5KV,1.2/50us |
Model specification::PMC96S-①-②-③-④-⑤ | |
① Model code: | |
1 | 57.7/100V Rated measurement voltage,5A Rated measurement current。 |
2 | 57.7/100V Rated measurement voltage,1A Rated measurement current。 |
3 | 220/380V Rated measurement voltage,5A Rated measurement current。 |
4 | 220/380V Rated measurement voltage,1A Rated measurement current。 |
② Model code: | |
1 | Power supply:85~264 VAC/45-65Hz,100~300 VDC 。 |
③ Model code: | |
0 | Without DI |
2 | 2 Channels DI |
④ Model code: | |
0 | Without relay output |
1 | Optional 1 channel relay output(RL1+、RL1- port) |
2 | Optional 2 channels relay output |
⑤ Model code: | |
ab | ab is a 2 integer,a means AI01 port optional for AI/AO modules, b means AI02portoptional for AI/AO 0 –none 1 - 0-5V DC analog input measure(AI) 2 - 4-20mA DC analog input measure(AI) 3 - 4-20mA DC analog output(AO) For example:ab = 00,meansnot equipped with AI/AOmodule ab = 21,Means AI01 port is equipped with 0-5V DC analog input measureAI/AOmodule, AI02 port is equipped with 4-20mA DC analog input measureAI/AOmodule |